3 Phase 350 KVA

350 kVA, 3 Phase, Standby Generating Set with Doosan engine, 500 litre fuel tank and remote start/stop controller. Optional canopy available.


Specifications

  • Power Rating: 350 kVA
  • Alternator Model: Crossley SLG Series
  • Engine Model: DOOSAN P126TI(S)
  • engine speed: 1500 rpm
  • Starter Voltage: 24 V
  • Frequency: 50 Hz
  • Cylinder No.: 6 TI
  • Cubic Capacity: 11.05
  • Bore / Stroke: 123 x 155 mm
  • Compression Ratio: 17.2 : 1
  • Aspiration: Turbo
  • Flywheel Max. Cont. Power: 300 kW
  • Combustion Air Flow: 23 m3/min
  • Cooling Air Flow: 540 m3/min
  • Heat Rejection to Cooling System: 273 kW
  • Exhaust Gas Flow: 58.1 m3/min
  • Exhaust Gas Temperature: 533 °C
  • Fuel Tank Capacity: 500 L
  • Approx. Fuel Consumption (1hr cont.): 71 L/hr
  • Approx. Fuel Consumption (1hr standby): 77 L/hr
  • Fuel Type: Diesel
  • Diam.: 3500 x 1200 x 1750 mm (L x W x H)
  • Weight: 2500 kg

Build Schedule

Standby: kVA @ 0.8 pf These ratings are applicable for supplying continuous electrical power (at variable loads) in the event of a utility power failure. No overload is permitted on these ratings. Minimum output from alternators are peak continuous rated (as defined in 1SO 8528-3 @ 27°C. Annual hour limitation: 500 hours).

Continuous: kVA @ 0.8 pf. (Divide standby rating by 1.1). Available for continuous electrical output. There is no hour limitation. 10% overload is available 1 hour in 12. The generating set and this specification is designed for environmental conditions of up to 27°C, up to 152.4 m above sea level and up to 60% relative humidity. Ratings at 0.8 pf.

For ratings outside this range, please contact us.

Control System

Standard Fitting: Starting is remote or local to the machine – close contacts to start, open contacts to stop.

Key start/stop with following meters:

  • Oil Pressure, Oil Temp, Motor Temp, Frequency, Volts and Amps
  • Shut Down for low oil
  • Emergency stop button
  • Output circuit breaker

Accessories

  • Muffler, stainless steel exhaust flex (20 kVA and above) and clamps, battery and leads, day fuel tank.
  • Oil and Coolant (within engine).
  • Circuit breaker and display for Amps, Volts and Frequency.

Options

  • Mains failure control system instead of standard remote control system with mains failure relay, and static battery charger (mains supplied).
  • Changeover contactors in separate cubicle.
  • Constant potential (static) battery charger fitted to key start/stop system or remote start/stop system.
  • Jacket Heater – Thermostatically controlled heater supplied and fitted to maintain engine coolant temperature at approximately 40°C.

Canopy Options

No.5-Canopy

All W&C canopies are made out of galvanised steel and are powder coated to offer you weather protection and to prolong the life of your generator. Our canopies have a unique soundproof insulation for quieter performance and are designed for easy maintenance and transportation.

Canopy No: No 5
Noise Level @ 1m: 85 dBA
Total Weight: 4000 kg (including Genset)
Dimensions (L x W x H): 4970 x 1230 x 2030 mm